IV. Adjustment of Components
1. Adjustment of Water Regulating Valve (water-cooled model only)
The water regulating valve or also called “water regulator” is factory-adjusted. No adjustment
is required under normal use. Adjust the water regulator , if necessary, using the following
procedures.
1) Attach a pressure gauge to the high-side line of the system. Or prepare a thermometer to
check the condenser drain temperature.
2) Rotate the adjustment screw by using a flat blade screwdriver, so that the pressure gauge
shows 260 PSIG (R-404A models/-F type), or the thermometer reads 100 -104°F, in 5
minutes after the icemaking process starts. When the pressure exceeds 260 PSIG, or the
condenser drain temperature exceeds 104°F, rotate the adjustment screw counterclock-
wise.
3) Check that the pressure or the condenser drain temperature holds a stable setting.
Adjustment Screw
Adjustment Screw
Bottom View
CW - Higher
CCW - Lower
CW
CCW