H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS

5

63-2579—3

CHECKOUT

CAUTION

Equipment Damage Hazard.
Can short electric circuitry.

• Never connect 120 Vac to the transducer.
• Connect only DC voltage to a transducer

intended for DC supply.

NOTE: Use laboratory quality meters and gauges for

applications requiring a high degree of accuracy.

1. Verify the transducer is mounted in the correct posi-

tion.

2. Verify appropriate input signal and voltage supply.
3. Verify appropriate configuration range.

Converting Output Signal to Percent RH

4 to 20mA Signal

Example: 12 mA output signal
(12 - 4)/ 0.16 = 50% RH

0 to 10 Vdc Signal

Example: 8 VDC transmitter signal output
8 Vdc/0.10 = 80% RH

Table 2. Troubleshooting.

signal [in mA] 4

0.16

-------------------------------------------------

percent RH

=

Problem

Items to Check

No reading

Verify correct supply voltage at the power terminal blocks.
Verify correct wiring configuration and DIP switch settings.
Verify that terminal screws are connected tightly with all wires firmly in place.

Erratic readings

Verify all wires are terminated properly.
Ensure that there is no condensation on the board.
Verify clean input power. In areas of high RF interference or noise, shielded cable can be

necessary to stabilize signal.