beautypg.com

Output settings (table 1), Outdoor mounting – Honeywell DUCT-MOUNT AND OUTDOOR-MOUNT H7625B User Manual

Page 2

background image

H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS

63-2579—3

2

Outdoor Mounting

The H7635C senses outdoor air humidity and
temperature. Mount this control where it can sense
average outdoor air humidity and temperature. Normally,
the north side of a building provides a suitable location.

NOTES:

H7635C is weatherproof for outdoor use.
Knockouts allow 1/2 in. conduit connection.

To avoid damaging board during installation,
the cover can be detached completely:

1.Carefully remove wire plug from board.
2.Set the cover aside.

1. Open case by rotating the cover counterclockwise.

NOTE: Orient case so the element points down.

2. Mount standard 1/2 in. conduit to the case.
3. Use case to mark mounting screw pilot hole

locations.

4. Drill pilot holes.
5. Fasten the case to the wall.
6. Wire the sensor. See Wiring section.

NOTE: The two free wires are thermistor wiring

connections. When connecting these, use
two wire nuts.

7. Reattach the wire plug and cover being careful not

to pinch wires between the cover and case.

Output Settings (Table 1)

The board has three switch blocks:
— A six DIP switch block.
— A four DIP switch block.
— A white gang switch on a blue block.

1. Adjust the 4-switch block according to Table 1.

NOTE: The 6-switch block normally requires no

adjustment. (See the Appendix.)

2. Set the gang switch (white switch in blue block) to

correspond with the output (mA or Vdc).

NOTE: See Fig. 1 for DIP switch locations.

Table 1. Controller Compatibility

and Output Settings.

Fig. 1. DIP switch locations and settings.

Controller

Required

Sensor

Output

Setting

4-Switch Block

Settings

Blue and

White

Output

Switch

L

ON

S

PEC

Setting

4 3 2 1

W7750, W7760,

W7761

4-20 mA — On — — 4-20 mA C7600C

W7750B,C

W7760C,

W7753, W7760

0-10 Vdc

(default)

On — — On Vout

H7621/31

T7350, XL50,

XL100,

XL500 XF

Modules, XFL

0-10 Vdc

(default)

On — — On Vout

n/a

Non-Honeywell 0-5 Vdc

On — On — Vout

n/a

M22705

NORMAL OPERATION

OFF

ON

OFF

ON

0-10 VDC

OFF

ON

4-20 MA

0-5 VDC

OFF

ON

This manual is related to the following products: