H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS

3

63-2579—3

WIRING

For voltage output, shielded cable (16-22 AWG) should
be used.

For current output, either shielded cable or twisted pair
(16-22 AWG) can be used.

NOTE: When using shielded cable, ground the shield

only at the controller end (see Fig. 2). Grounding
both ends can cause a ground loop.

The 20K ohm NTC temperature output is accessed
through the separate blue and green wires (located inside
the enclosure).

Fig. 2. Typical wiring diagram for transducer with two-

wire mA output and external DC power supply.

Fig. 3. Humidity sensor (0-10 Vdc output) wiring with T7350

(use with RH/Temperature combination T7350 units only).

mA OUTPUT

TRANSDUCER

ONLY

18 TO 36 Vdc

POWER SUPPLY

CONTROLLER, METER
OR RECORDER

INPUT SIGNAL

COMMON

Vin

+

+

Io

M22528

GROUND

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD.

HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER.

USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.

HC AND HP PROVIDE 24 VAC TO THE HUMIDITY SENSOR.

1

M22529

2

3

2

3

4

5

5

RC

X

T7350
SUBBASE

W1

G

T7770 REMOTE SENSOR

Y1

W3/Y4 Y3

W2

Y2

AUX

RH

T5

T6

T7

T4

T3

DISCHARGE
AIR
SENSOR

OUTDOOR
AIR
SENSOR

MOTION
SENSOR

HUMIDITY SENSOR

M

OS

OS

AS

AS

M

HC

HP

HS

Gnd

Vin

(Vac)

Vo

(0-10 Vdc)

1

4

L1

(HOT)

L2

COMPRESSOR
CONTACTOR 1

COMPRESSOR
CONTACTOR 2

HEAT
RELAY 1

1

2

3

4

5

6

7

8

9

FAN
RELAY

ECONOMIZER

HEAT
RELAY 2

COMPRESSOR
CONTACTOR 3

COMPRESSOR
CONTACTOR 4

This manual is related to the following products: