OM-480 Page 21

6-2.

240 Volt Duplex Receptacle (Optional)

Ref. ST-188 448 / ST-174 408

Y

If unit does not have GFCI re-
ceptacles, use GFCI-pro-
tected extension cord.

1

240 V 15 A AC Receptacle
RC1

Receptacle supplies 60 Hz single-
phase power at weld/power speed.
Maximum output is 3 kVA/kW.

2

Circuit Breakers CB1 And
CB2

CB1 and CB2 protect the
receptacles from overload. If CB1
or CB2 opens, the 240 V receptacle
and half of the 120 V receptacle
does not work. 120 volts may still be
present at the 240 V receptacle.

.

If a circuit breaker continues to
open, contact Factory Autho-
rized Service Agent.

Combined output of all receptacles
is 3 kVA/kW. Auxiliary power is not
affected by weld output.

EXAMPLE: If 10 A is drawn from the
240 V receptacle, only 5 A is avail-
able at the 120 V receptacle:

(240 V x 10 A) + (120 V x 5 A) = 3.0
kVA/kW