Operator Interface Products
HMi Operator Interface
Software and Accessories
Table 12. HMIEC0806/HMIEC1612 Function Specifications
ᕃ
M1000, M1001, M1002, M1003, M1020, M1021, M1022, M1067, M10068, and M1161 are the
special auxiliary relays (special M).
Item
Specifications
Remark
Control Method
Stored program, cyclic
scan system
—
I/O Processing Method
Batch I/O (refresh)
Immediate refresh command available only
with I/O of the MPU
Execution Speed
Basic command (30 us)
Application command (30 ~ hundreds us)
Program Language
Commands + Ladder
Diagram + SFC
Step commands included
Program Capacity
999 Steps
Built-in EEPROM
Commands
Basic commands: 32
(including the STL
commands)
Application commands: 59
Step Relay
(Latched)
General Step
Point
128 Points
S0 ~ S127
Auxiliary
Relay
General
1024 Points
M0 ~ M511, M768 ~ M999, 744 points;
M1000 ~ M1279, 280 points
ᕃ
Latched
256 Points
M512 ~ M767
Timer
Digital
64 Points
T0 ~ T63 (100 ms time base)
63 Points
T64 ~ T126 (10 ms time base)
1 Points
T127 (1 ms time base)
Counter
General
112 Points
C0 ~ C111
Latched
16 Points
C112 ~ C127
32 bit
13 Points
C235,C236,C237,C238,C241,C242,
C244,C246,C247,C249,C251,C252, C254
(all of them are latched type)
Data
Register
General
408 Points
D0 ~ D407
Latched
192 Points
D408 ~ D599
Pointer
P
64 Points
P0 ~ P63
Index
Register
E / F
2
E, F
Constant
Decimal K
16 bit: -32768 ~ +32767
32 bit: -2147483648 ~ +2147483647
Hexadecimal H 16 bit: 0000 ~ FFFF
32 bit: 00000000 ~ FFFFFFFF
Self Diagnosis / Protection
I/O check, system execution timeout check, invalid command check,
program check and password settings
Monitor / Debug
Program execution time display, bit / word, device settings