Operating Instructions and Owner’s Manual

Enerco | enerRadiant® XL Series Heater

SECTION 8: Troubleshooting Guide. Ener-Radiant XL

START

Turn on thermostat

Does blower turn

on?

Yes

Does the igniter

warm up and glow

red?

Yes

No

Check Thermostat

and Wiring. Is the

power supply to unit

115V?

No

Find the source

of the electrical

problem

Check LED indicator on SmartValve for

indication of fault. Refer to SmartValve testing

on page ?? to determine problem.

No

Is the air intake or

exhaust blocked?

Yes

Remove Obstruction

Check wiring and

connections

No

Is the ignitor

damaged?

No

Check voltage at

ignitor. Is it 115V

during ignition

cycle?

Yes

Is blower side door

in place?

No

Replace door

No

Check wiring and

hose connection to
air switch. Are they

OK?

Yes

Is the voltage at

the transformer
secondary 24V?

No

Is the voltage at the
transformer primary

115V

Replace ignitor.

Yes

No

Is the resistance

through igniter 40

to 75 ohms?

Remove door. Is

voltage at door

switch 115V?

Yes

No

Check voltage at

gas valve.

Check for 115V transformer input at plug C3

on SmartValve. Check for 115V output of

C3. If no output voltage is present replace

SmartValve.

Replace wiring and/
or hose connection.

No

Jumper wires at
pressure switch.

Does the ignitor

glow red?

Yes

Replace transformer

Yes

Check wire

connections.

Yes

Depress switch.

Does blower come

on?

Yes

Yes

No

Check voltage to

motor. Is it 115V?

Yes

Is the blower fan

obstructed?

No

Replace blower

motor.

Replace pressure

switch.

Yes

Replace SmartValve.

No

Check LED indicator on SmartValve for

indication of fault. Refer to SmartValve testing

on page ?? to determine problem.

Check door fit. If

damaged, replace

door.

Replace switch.

No

Remove obstruction

Yes

After ignitor warm-

up period, does the

valve click?

Yes

Does the burner

light?

Yes

Does the burner

stay on?

Yes

Does the burner
run until the call

for heat ends?

If a problem still exists, contact Enerco Technical Products Customer Service

1-800-251-0001

No

The SmartValve checks the status of the blower proving switch contacts must see a change in the

contact with every firing cycle. Placing a jumper at the switch out of sequence will result in a fault with

the LED indicator flashing two times.

Were the gas lines purged of air?

No

No

Yes

Check inlet gas pressure. Is pressure correct?

Refer to page 40 for correct pressure for unit.

Yes

Check inlet gas shutoff. Adjust regulator.

Contact gas supplier

Is the continuity of

the ground wire

OK?

No

The switch on the gas valve must be in the on

position and the line purged of air.

No

Repair wiring.

No

Check the continuity of the ground wire.

Check the thermostat.

Check outlet gas pressure during ignition cycle.

Is the pressure 3.5” w.c. for natural or 10.5”

w.c. for lp?

Yes

Adjust to proper pressure.

No

Are L1 and L2

reversed?

Yes

Yes

Repair wiring

Is the wiring at the

SmartValve OK?

No

Repair wiring

Is the insulation on

the sensor lead OK?

No

Repair wiring

No

Yes

Yes

Are the wires to

the SmartValve OK?

Yes

Replace SmartValve

No Replace/repair wires.

Yes

Check for proper

burner orifice and

air plate.

Is the sensor

positioned

properly?

Yes

Is the sensor dirty?

No

Replace Sensor

No

Repair/Replace

Yes

Clean sensor.

A fault indication of six flashes may indicate

that the flame sensing circuit is not functioning

properly. Perform the following series of checks

to correct the problem.