Enerco | enerRadiant® XL Series Heater

Operating Instructions and Owner’s Manual

Natural outlet pressure should be 3.5”

LP inlet pressure should be 11.0”

LP outlet pressure should be 10.25”

3. Check for proper orifice and air plate.

Burner Does Not 1. Check ground wire continuity.

Stay Lit: 2. Check burner internal wiring for reversed

leads.

3. Check insulation on the igniter leads.

4. Replace module if necessary.

Honeywell Valve LED Status

The Ener-Radiant XL series Tube Heater is equipped with a honeywell
Smart Valve. This valve has a built-in diagnostic program, which will
assist in troubleshooting in the event of a valve-related problem. The
LED or (Light Emitting Diode) is located on the top of the valve as
shown in diagram below. The LED status indications are listed below
to help with the troubleshooting.

FIGURE 22:

OFF

INDICATED

Off

No power to the control

Bright-Dim

Normal operation.

This indication shows whenever the system is

powered, unless some abnormal event has occurred.

2-Flashes

Airflow providing switch remains closed longer than

30

seconds after call for heat begins (air providing

switch

stuck closed.)

3-Flashes

Airflow providing switch remains open longer than 30

seconds after combustion air blower is energized - or

blower does not energize.

4-Flashes

White jumper wire is loose.

5-Flashes

Flame signal sensed out of proper sequence.

6-Flashes

System Lockout.

LED