Installation – Enviro WINDSOR 50-1578 User Manual
Page 14
Storm Collar
Roof Flashing
Roof Rafters
Fire Stop with
Support Collar
Ceiling Joist
Vertical Vent Pipe
Clean Out Tee
with Pipe Adapter
ENVIRO Windsor
Note:
All vent sections must maintain
3" (75mm) clearances to
combustibles.
Rain cap - ensure cap is at
least 900mm (3 feet) above
the roof at the lowest point
Installation
I
NSIDE
V
ERTICAL
I
NSTALLATIONS
:
1. Choose a stove location that is ideal. See the section “D
ECIDING
W
HERE
TO
L
OCATE
YOUR
P
ELLET
A
PPLIANCE
.”
2. Place a non-combustible hearth pad where necessary.
3. Place the unit on the hearth pad (if installed on a carpeted surface) and space the unit in a manner
Figure 13: Inside Vertical Installation.
so when the pellet vent is
installed vertically, it will be
100mm (4”) away from a
combustible wall.
4. Locate the center of the fresh
air intake pipe on the unit.
Match that center with the
same point on the wall and
cut a hole about 40mm (15⁄8”)
in diameter.
5. Install the fresh air intake
pipe.
6. Install the tee with clean out.
7.
I
nstall the pellet vent upward
from there. When you reach
the ceiling, make sure that the
vent goes through the ceiling
fire stop. Maintain a 100mm
(4”) distance to combustibles
and keep attic insulation away
from the vent pipe. Maintain
an effective vapor barrier.
8. Finally, extend the pellet
vent to go through the roof
flashing.
9. Ensure that the rain cap is
approximately 900 mm (36”)
above the roof.
14