beautypg.com

Installation – Enviro WINDSOR 50-1578 User Manual

Page 14

background image

Storm Collar

Roof Flashing

Roof Rafters

Fire Stop with

Support Collar

Ceiling Joist

Vertical Vent Pipe

Clean Out Tee

with Pipe Adapter

ENVIRO Windsor

Note:

All vent sections must maintain

3" (75mm) clearances to

combustibles.

Rain cap - ensure cap is at

least 900mm (3 feet) above

the roof at the lowest point

Installation

I

NSIDE

V

ERTICAL

I

NSTALLATIONS

:

1. Choose a stove location that is ideal. See the section “D

ECIDING

W

HERE

TO

L

OCATE

YOUR

P

ELLET

A

PPLIANCE

.”

2. Place a non-combustible hearth pad where necessary.
3. Place the unit on the hearth pad (if installed on a carpeted surface) and space the unit in a manner

Figure 13: Inside Vertical Installation.

so when the pellet vent is

installed vertically, it will be

100mm (4”) away from a

combustible wall.

4. Locate the center of the fresh

air intake pipe on the unit.

Match that center with the

same point on the wall and

cut a hole about 40mm (15⁄8”)

in diameter.

5. Install the fresh air intake

pipe.

6. Install the tee with clean out.
7.

I

nstall the pellet vent upward

from there. When you reach

the ceiling, make sure that the

vent goes through the ceiling

fire stop. Maintain a 100mm

(4”) distance to combustibles

and keep attic insulation away

from the vent pipe. Maintain

an effective vapor barrier.

8. Finally, extend the pellet

vent to go through the roof

flashing.

9. Ensure that the rain cap is

approximately 900 mm (36”)

above the roof.

14