Setting jumpers, Install the module in the rack, Setting – ProSoft Technology MVI46-GSC User Manual
Page 9: Jumpers

Start Here
MVI46-GSC ♦ SLC Platform
Generic Serial Communication Module
ProSoft Technology, Inc.
Page 9 of 78
December 5, 2007
1.3 Setting
Jumpers
If you use an interface other than RS-232 (default), you must change the jumper
configuration to match the interface. The following illustration shows the MVI46-
GSC jumper configuration:
The Setup Jumper acts as "write protection" for the module's flash memory. In
"write protected" mode, the Setup pins are not connected, and the module's
firmware cannot be overwritten. Do not jumper the Setup pins together unless
you are directed to do so by ProSoft Technical Support.
1.4
Install the Module in the Rack
If you have not already installed and configured your SLC processor and power
supply, please do so before installing the MVI46-GSC module. Refer to your
Rockwell Automation product documentation for installation instructions.
Warning:
You must follow all safety instructions when installing this or any other
electronic devices. Failure to follow safety procedures could result in damage to
hardware or data, or even serious injury or death to personnel. Refer to the
documentation for each device you plan to connect to verify that suitable safety
procedures are in place before installing or servicing the device.
After you have checked the placement of the jumpers, insert MVI46-GSC into the
SLC™ chassis. Use the same technique recommended by Rockwell Automation
to remove and install SLC™ modules.
Warning: This module is not hot-swappable!
Always remove power from the rack
before inserting or removing this module, or damage may result to the module, the
processor, or other connected devices.