beautypg.com

Status data, 2 status data – ProSoft Technology MVI46-GSC User Manual

Page 20

background image

MVI46-GSC ♦ SLC Platform

Installing and Configuring the Module

Generic Serial Communication Module

Page 20 of 78

ProSoft Technology, Inc.

December 5, 2007

2.2.2 Status

Data

This data area holds the status data transferred from the module. The following
table lists the data contained in this data area.

Object in
GSCInStat

M1: File
Offset

Description

PassCnt

260

Program cycle counter

Product

261 to 262 Product name as ASCII string

Rev

263 to 264

Revision level as ASCII string

OP

265 to 266 Operating system level as ASCII string

Run

267 to 268

Run number as ASCII string

BlkErrs.Read

269

Number of blocks transferred from module to processor

BlkErrs.Write

270

Number of blocks transferred from processor to module

BlkErrs.Parse

271

Number of blocks parsed by module

BlkErrs.Err

272

Number of block errors in module

Port[0].RxState

273

Port 1 receive state:
–1 = Listening for data
1 = Receiving Port Data
2 = Waiting for Backplane transfer

Port[0].RXCharCnt

274

Port 1 receive character count

Port[0].RxMsgCnt

275

Port 1 receive block count

Port[0].TxState

276

Port 1 transmit state:
0 = Waiting for Data to Send
1 = RTS On
2 = RTS Timeout
3 = Sending data
4 = Waiting for RTS Off
5 = RTS turned off
30 = Intercharacter Delay
31 = Intercharacter Delay
32 = Intercharacter Delay
100 = Message Delay before Transmit
101 = Message Delay before Transmit

Port[0].TxCharCnt

277

Port 1 transmit character count

Port[0].TxMsgCnt

278

Port 1 transmit block count

Port[0].ErrorWord

279

Port 1 error word

Port[1].RxState

280

Port 2 receive state:
–1 = Listening for data
1 = Receiving Port Data
2 = Waiting for Backplane transfer

Port[1].RXCharCnt

281

Port 2 receive character count

Port[1].RxMsgCnt

282

Port 2 receive block count