ProSoft Technology MVI56E-MCMR User Manual
Page 40

Start Here
MVI56E-MCMR ♦ ControlLogix Platform
User Manual
Modbus Communication Module with Reduced Data Block
Page 40 of 225
ProSoft Technology, Inc.
May 13, 2014
1 In the C
ONTROLLER
O
RGANIZATION
window, expand the D
ATA
T
YPES
and
U
SER
-D
EFINED
folders, and then double-click MCMRDATA.
This action opens
an edit window for the MCMRDATA data type.
2 In the edit window, change the value of the R
EAD
D
ATA
array from INT[600] to
INT[1000] as shown, and then click A
PPLY
.
Note: If RSLogix resets your data values, refer to the backup copy of your program to re-enter your
configuration parameters.
Important: When you change the ReadData and WriteData array sizes in RSLogix, you must also
change the Read Register Count and Write Register Count values in ProSoft Configuration Builder
3 In ProSoft Configuration Builder, navigate to the B
ACKPLANE
C
ONFIGURATION
tag (page 56), and double click to open an edit window. Change the R
EAD
R
EGISTER
C
OUNT
value to match the value you entered in RSLogix for the
ReadData data type.