Optional test, Options – Retrotec DucTester 200 series with DM32 User Manual

Page 7

background image

Connect Flex Duct to fan exhaust.

Check that tubing is connected the same as for

depressurize test (step 3).

Conduct test (step 4).

Duct Leakage to Outdoors:

Pressurize

Follow depressurize test method (page 6) except both

fan directions are reversed.

Page 7 of 8

Total Duct Leakage: Pressurize

Optional Test

Pressurizing can blow the Grill Mask off the registers!

Options

pressurize

Inlet

airflow

Exhaust

Pass the Flange through the 10 inch hole in the

Flow Hood and tape it inside.

Attach the Flex Duct.

Secure the Flow Hood over the register

To measure Duct leakage:

Connect the Flex Duct to the fan and test as usual.

To measure HVAC System Flow:

For measuring supply flows, attach the Flex Duct

to the inlet (suction) side of the fan.

For measuring return flows, attach the Flex Duct

to the exhaust (discharge) side of the fan.

Connect the Umbilical to the DucTester.

Attach the blue tube to the Flow Hood and gauge.

Tap [Channel B] and select “Flow: CFM”

When a definite pressure appears on [Channel A]:

Tap [Set Speed] and adjust with Jog keys until

[Channel A] shows close to 0 pressure.

Or

Tap [Set Pressure] [0] to have the DucTester

automatically achieve a 0 pressure.

Read the HVAC system flow result directly from

the gauge

Using the optional Flow Hood

Connect it quickly to ceiling level returns to measure

duct leakage or use it with your DucTester as a Pow-

ered Flow Hood to accurately measure HVAC system

flow rates.

Flow Hood

blue tube