beautypg.com

Retrotec DucTester 200 series with DM32 User Manual

Page 2

background image

Make sure DucTester 240 is showing on the
Home screen with “Mid” Range.

If not, tap the fan picture, then

Tap , tap DucTester 240, thenthen select
the range that you have installed.

Tap on [Channel B] to change the type of result
or units. Select based on “Get the results you
need” on page 4.

Tap [Settings] then [Time averaging] and
select 5 seconds.

Tap [Settings] then .

Make sure the [Default @ Pressure] is 25 Pa.
Make sure “n” value is set to 0.60 for Ducts.

Tap to return to the Home screen.

Step 1:

Prepare ducts and house

Seal all supply and return grills/registers, including

any exterior air inlets, with Grill Mask or tape.

Open all interior doors leading to rooms containing

a supply or return register, and open an exterior door

or window.

Shut off all HVAC (exhaust fans, dryers, A/C, furnaces).

Page 2 of 8

Step 2:

Connect to ducts

Turn off air-handler

and remove all filters.

Tape Flange to main

return or air handler

cabinet using

masking tape.

Attach Flex Duct to

Flange.

Install Mid-Range Ring to start,

as most systems can be tested

on this Range Configuration.

Tap

on gauge and select

range to match fan,

whenever a Range Ring is changed.

Prepare the gauge

Mid

Low

Open

Remove Range Rings for

leakier ducts, add Rings

for tighter ducts.

Next, prepare the ducts, house and fan following Steps

1 through 3.