To measure the air leakage from the

duct system to outdoors requires both a

DucTester and a Blower Door system.

The Door Fan depressurizes the house

and the DucTester depressurizes the

ducts so leakage from the duct system

back into the conditioned space of the

home is neutralized.

Method #1:

Method #2:

Connect the red T-connected tubes to red ports

and all other tubes per diagram.

Tap [Set Pressure] [25] [Enter] on DucTester

gauge then on Door Fan gauge.

Tap [@ Pressure] on DucTester gauge to display

the results “@25Pa”.

When “-25 Pa” +/– 1 is achieved on both gauges,

record duct leakage to outdoors from the DucTester

gauge.

Connect tubes to gauges per diagram.

With DucTester off,

Set the Door Fan gauge to -25 Pa

by tapping [Set Pressure] [25] [Enter].

Set the DucTester to “0 Pa” by tapping

[Set Pressure] [0] [Enter].

When “0 Pa” +/– 1 is achieved, record

duct leakage to outdoors from DucTester gauge.

Method 1 uses the DucTester set up the

same was as for the Total Duct Leakage

test, and allows use of the [@ Pressure] to

increase accuracy.

Results are easier to visualize since both

the duct and house pressures can be seen.

Method 2 does not require connecting a

red tube to the DucTester gauge, but

[@ Pressure] cannot be used while setting

to 0 pressure.

DucTester at 0 Pa, Door Fan at -25 Pa

**

Both gauges at -25 Pa

**

Door Fan gauge

DucTester gauge

Optional Test

Duct Leakage to Outdoors: Depressurize

Options

**

If 50 Pa test pressure required, use 50 in all instructions.

Method# 1