Setting numeric values, Programming the meter – Precision Digital PD662 User Manual
Page 15

PD662 Loop-Powered Meter
Instruction Manual
15
Setting Numeric Values
The numeric values are set using the Right and Up arrow buttons.
Press Right arrow to select next digit and Up arrow to increment digit.
The two left-most digits on the display are set as a single digit, able to
display -19 to 29.
The digit being changed blinks.
Press the Enter button, at any time, to accept a setting or Menu button
to exit without saving changes.
The decimal point is set using the Right or Up arrow button in the
Setup-decimal point menu.
Programming the Meter
It is very important to read the following information, before proceeding
to program the meter:
• There
is
no need to recalibrate the meter for milliamps when first
received from the factory.
• The meter is factory calibrated for milliamps prior to shipment.
The calibration equipment is certified to NIST standards.
• Use
the
Scale (SCL) menu to enter scale parameters without
applying a live signal.
• Alternatively, use the Calibrate (CAL) menu to apply a signal from a
calibrator or a 4-20 mA transmitter to calibrate the meter.
Inputs may be calibrated or scaled to any display within the range of the
meter.
Additional parameters, not needed for most applications, are viewed
and programmed with the Advanced Features menu, see Advanced
Features Menu on page 20.