Mounting, Pd662 connections – Precision Digital PD662 User Manual
Page 10

PD662 Loop-Powered Meter
Instruction Manual
10
Mounting
The PD662 can be wall mounted using the mounting holes beneath the 
cover screws. A ½” NPT pipe conduit hole is provided. It can be panel 
mounted with the addition of the PDA6624 panel mount kit. It can also 
be pipe mounted by using the PDA6845 pipe mount kit. 
Refer to Mounting Dimensions, page 28 for details on wall or panel 
space requirements. 
The unit shall be installed in a way that will prevent 
any accidental contact of the internal meter circuits 
and power supply lines. 
Cable suitable for outdoor use and a CSA Approved 
gland rated 4X, or a suitable conduit and a CSA 
Approved connector rated 4X, is intended to be used 
in final installation. 
Metallic conduit shall be reliably bonded to protective 
earth/ground without creating any ground loop.
PD662 Connections
Disconnect power before opening the unit.
 
To access the connectors, remove the enclosure cover and unscrew the 
two captive stainless steel screws on the rear mounting board. Remove 
the meter assembly from the enclosure. Signal connections are made to a 
three-terminal removable connector. The signal wiring terminal block is on 
the rear of the meter assembly. 
S+
4-20 mA signal input positive terminal connection
S-
4-20 mA signal return/negative terminal connection
X
Not connected (no backlight option)
B-
4-20 mA signal return/negative terminal when using the 
installed loop powered backlight option 