beautypg.com

MEDC CU1 User Manual

Page 6

background image





Type 5.

The supply should be connected to T1 (+ve) & T2 (-ve), loop out on T3, T4 respectively. The initiate supply

should be connected to T5 (+ve / live) & T6 (-ve / neutral), loop out on T7 & T8 respectively.


Type 6.

The supply should be connected to T1 (sounder +ve), T2 (common -ve1) & T3 (common -ve2), loop out on

T4, T5 & T6 respectively. The independent +ve supply for the beacon should be connected to T7, loop out on T8.


Type 7.

The supply should be connected to T1 (L) & T2 (N), loop out on T3 & T4 respectively.


Type 8.

The supply should be connected to T1 (L) & T2 (N), loop out on T3 & T4 respectively. The initiate supply

should be connected to T5 (+ve / live) T6 (-ve / neutral), loop out on T7 & T8 respectively.


Type 9.

The supply for the sounder should be connected to T1 (L) & T2 (N), loop out on T3 & T4 respectively.

The supply for the beacon should be connected to T5 (L) & T6 (N), loop out on T7 & T8 respectively


The dual stage units can be switched between the two stages by either:

a. Reversing the polarity of the supply (2 wire connection), or

b. Connecting as a three wire common +ve system and switching between the two –ve lines

i.e. with T1 (+ve) & T2 (-ve), stage 1 is active

a. With T1 (-ve) & T2 (+ve) stage 2 is active or

b. With T1 (+ve) & T3 (-ve) stage 2 is active


Note:

With type 5 units (see details above), the dual stage sounder will only be connected with 2 wires and the

second stage can only be selected by reversing the polarity (option a. above)


Tone Selection:

On the AC input units, the required tone is selected by means of a 5-way DIL switch mounted on the top face of the

xenon PCB assembly


On the DC input units, tone 1 & 2 are selected using the two 5-way DIL switches (marked SW1 & SW2) mounted

on the top face of the xenon PCB assembly

09/14

© MEDC 2014