beautypg.com

MEDC XB15 User Manual

Page 5

background image

© MEDC 2014

06/14



















































































5.0 SPECIAL CONDITIONS FOR SAFE USE

1. Painting and other surface finishes, other than those applied by the manufacturer, are not permitted

2. In order to maintain the dust tight integrity of the enclosures (IP6X), the threads of cable entry devices and

stopping plugs shall be sealed in accordance with the applicable code of practice for flameproof installation

6.0 CERTIFICATION/APPROVALS

IECEx units

Certified to IEC60079-0, IEC60079-1 and IEC61241-1-1

Ex d unit (IEC certification No. IECEx BAS 05.0048X)

Ex d IIC T

A

135°C (-55°C to +70°C)

T

A

100°C (-55°C to +55°C)

T

A

85°C (-55°C to +40°C)


The IECEx certificate and product label carry the IECEx equipment protection level marking

Ex d IIC

Dip A21 IP6X

Where Dip signifies suitability for use in the presence of dust

Where A21 signifies suitability for use in the presence of dust in a zone 21 area

ATEX units

Certified to EN50014, EN50018 and EN50281-1-1

EEx d unit (ATEX certification No. Baseefa04ATEX0009X)

EEx d IIC T135°C (-55°C to +70°C)

T100°C (-55°C to +55°C)

T85°C (-55°C to +40°C)

The ATEX certificate and product label carry the ATEX group and category marking:

II 2 GD

Where:

Signifies compliance with ATEX

II

2

G

D


The ATEX certificate and product label also carry the following mark:

This signifies unit compliance to the relevant European directives, in this case 94/9/EC, along with the number of

the notified body issuing the EC type examination certificate.

Signifies suitability for use in surface industries

Signifies suitability for use in a zone 1 area

Signifies suitability for use in the presence of gases

Signifies suitability for use in the presence of dust