19-FAULTS/CAUSES/SOLUTIONS

ANOMALY

POSSIBLE CAUSES

SOLUTIONS

The product works for a few minutes

and then switches off.

Start-up phase is not completed.

Repeat start-up.

Temporary power cut.

Switch it back on.

Clogged smoke duct.

Clean the smoke duct.

Faulty or malfunctioning temperature

probes.

Check and replace the probes.

Pellets accumulate in the brazier, the

glass of the door gets dirty and the

flame is weak.

Insufficient combustion air.

Make sure that the air inlet in the room is

fitted and clear.

Clean the brazier and check that all the

holes are clear.

Perform a general cleaning of the

combustion chamber and the smoke duct.

Check the condition of the door gaskets.

Damp or unsuitable pellets.

Change the type of pellets.

Faulty smoke evacuation motor.

Check the motor and replace it, if

necessary.

The smoke evacuation motor does

not work.

No electrical supply to the stove.

Check the mains voltage and the

protection fuse.

The motor is faulty.

Check the motor and capacitor and replace

them, if necessary.

Defective circuit board.

Replace the circuit board.

The control panel is broken.

Replace the control panel.

The convection air fan never stops.

Thermal probe defective or faulty.

Check the probe and replace it, if necessary.

Fan faulty.

Wait a few minutes and check motor

operation, replace it if necessary.

The product has not reached the shutdown

temperature yet.

Wait.