Thermostats are not approved on vented decorative appliances.

Label all wires prior to disconnection when servicing controls.

Wiring errors can cause improper and dangerous operation. Verify

proper operation after servicing.
The millivolt gas valve does not require 24 or 110 volts. The gas

valve is powered by the thermopile. See Figure 16 to provide

optional wall switch, thermostat, or remote control. Maximum

length of 20 feet of 16 AWG to conductor wires is to be used with

all optional switches.
Use the red and green leads from the rocker switch that are wire

nutted together to attach optional components.
Check System Operation

Millivolt system and all individual components may be checked

with a millivolt meter 0-1000 MV range.
Remote Receiver -VFSUR-(18, 24, 30)

Use the following steps to place the remote receiver adjacent to

the gas valve.
Attention:

1. The remote receiver can not be placed behind the gas valve and

burner assembly.

2. When facing the appliance, the remote receiver must be placed

to the right of the gas valve and burner assembly.

Note: Do not let remote control receiver come in contact with

burner assembly.
On circulating vent-free firebox, install remote control receiver

behind bottom louver.
Refer to remote control installation and operating instructions for

more details on remote control.
750 Millivolt System

When you ignite the pilot, the thermocouple produces millivolts

(electrical current) which energizes the magnet in the gas valve.

After 30 seconds to 1 minute time period you can release the gas

control knob and the pilot will stay ON. Allow your pilot flame to

operate an additional one (1) to two (2) minutes before you turn the

gas control knob from the PILOT position to the ON position. This

time period allows the millivolts (electrical current) to buildup to a

sufficient level allowing the gas control to operate properly.
Millivolt Control

The valve regulator controls the burner pressure which should be

checked at the pressure test point. Turn captured screw counter

clockwise 2 or 3 turns and then place tubing to pressure gauge over

test point (Use test point “out” closest to control knob). After taking

pressure reading, be sure and turn captured screw clockwise firmly

to re-seal. Do not over torque. Check for gas leaks.

WIRING

REMOTE/OFF/ON SWITCH

A DISTANCE/FERME/OUVERT

INTERRUPTEUR

THERMOPILE

GAS VALVE

THERMOCOUPLE

(NATURAL)

OFF

ON

REMOTE

(OPTIONAL) REMOTE CONTROL RECEIVER

(FACULTATIVE) CONTROLE E DISTANCE

DU RECEPTEUR

(OPTIONAL) WALL SWITCH

INTERRUPTEUR MURAL

(FACULTATIVE)

(OPTIONAL) THERMOSTAT

(FACULATIVE) THERMOSTAT

GAS VALVE

VALVE DE GAZ

REMOTE/OFF/ON SWITCH

A DISTANCE/OUVERT/

FERME INTERRUPTEUR

REMOTE CONTROL RECEIVER/

THERMOSTAT/ CONTROLE E

DISTANCE DU RECEPTEUR

H

N

PILOT

VEILLEUSE

THERMOCOUPLE

(LPG)

Figure 17

Valve View for Operating Sequence

Figure 16

VFSUR Wiring Diagram