beautypg.com

Horizontal exhaust through wall installation, Installation – Enviro C-10608 User Manual

Page 18

background image

18

�� �

���� ����

���� �������

���� �������

�������� ���� �������

����������� ���

Installation

H

ORIZONTAL

E

XHAUST

T

HROUGH

W

ALL

I

NSTALLATION

:

Vent installation: install vent at clearances specified by the vent manufacturer.

A chimney connector shall not pass through an attic or roof space, closet or similar concealed spaces,

or a floor, or ceiling. Where passage through a wall or partition of combustible construction is desired,

the installation shall conform to CAN/CSA-B365 Installation Code for Solid-Fuel-Burning Appliances and

Equipment. Only use venting of L or PL type with an inside diameter of 3 or 4 inches (7.6 or 10.1 cm).
1. Choose a location for your stove that meets the requirements stated in this manual and allows

installation with the least amount of interference to house framing, plumbing, wiring, etc.

2. Install a non-combustible hearth pad (where necessary).

3. Place the appliance 15” (37.5 cm) away from the wall. If the stove is to be set on a hearth pad, set

the unit on it.

4. Locate the center of the exhaust pipe on the stove. Extend that line to the wall. Once you have located

the center point on the wall, refer to pellet vent manufacturer installation instructions for correct hole

size and clearance to combustibles.

5. Install the wall thimble as per the instructions written on the thimble. Maintain an effective vapour

barrier in accordance with local building codes.

6. Install a length of 3” (76 mm) or 4” (101 mm) vent pipe into the wall thimble. The pipe should install

easily into the thimble.

7. Install the fresh air intake (see O

UTSIDE

F

RESH

A

IR

C

ONNECTION

).

8. Connect the exhaust vent pipe to the exhaust pipe on the stove. Seal the connection with high

temperature silicone.

9. Push the stove straight back, leaving a minimum of 2” (5 cm) clearance from the back of the stove to

the wall. Seal the vent pipe to the thimble with high temperature silicone.

10. The pipe must extend at least 12” (30 cm) away from the building. If necessary, bring another length

of pipe (PL type) to the outside of the home to connect to the first section. Do not forget to place

high temperature silicone around the pipe that passes through the thimble.

11. Install a vertical pipe, or if all requirements for direct venting are met, install vent termination. The

stainless steel cap termination manufactured by the vent manufacturer is recommended. However,

when the vent terminates several feet above ground level and there are no trees, plants, etc. within

Figure 14: Straight through wall Installation.

several feet, a 45° elbow can be used as

termination. The elbow must be turned

down to prevent rain from entering.

NOTE:

• Some horizontal through wall installations

may require a “T” and 3 to 5 feet (91 to 152

cm) of vertical pipe outside the building to

help naturally draft in the unit.

• This may be required if a proper burn cannot

be maintained, after the stove has been tested

and the airflow set.

• This is due to the back pressure in the exhaust

caused by airflow around the structure.

• All sections of pipe must have three (3) screws

evenly spaced and all horizontal vent sections

must have a bead of high temperature silicone

installed on the male end of the pipe before

installation to create a gas tight seal.