ENVISION SERIES INSTALLATION MANUAL

Air Handler Coil Data

Notes: * Variable speed air handler required for all dual capacity units.

Line Set Sizes

Envision

Split Model

Matching Air

Handler

Coil Surface

Area (sq ft.)

FPI

Rows

Tube

Diameter

022 - 038

042 - 072

NAH060

5.83

12

3

3/8"

NAH036

5.83

12

2

3/8"

Unit

Air

Factory

Size

Handler

Suction

Liquid

Suction

Liquid

Suction

Liquid

Charge (oz.)

NZ022

NAH036

5/8" OD

3/8" OD

5/8" OD

3/8" OD

3/4" OD

3/8" OD

56

NZ030

NAH036

5/8" OD

3/8" OD

3/4" OD

3/8" OD

3/4" OD

3/8" OD

56

NZ036

NAH036

5/8" OD

3/8" OD

3/4" OD

3/8" OD

3/4" OD

1/2" OD

56

NZ042

NAH060

3/4" OD

3/8" OD

3/4" OD

3/8" OD

7/8" OD

1/2" OD

74

NZ048

NAH060

3/4" OD

3/8" OD

7/8" OD

3/8" OD

7/8" OD

1/2" OD

90

NZ060

NAH060

7/8" OD

1/2" OD

7/8" OD

1/2" OD

1-1/8" OD

1/2" OD

92

NZ070

NAH060

7/8" OD

1/2" OD

7/8" OD

1/2" OD

1-1/8" OD

1/2" OD

108

NZ026

NAH036

5/8" OD

3/8" OD

3/4" OD

3/8" OD

3/4" OD

1/2" OD

52

NZ038

NAH036

5/8" OD

3/8" OD

3/4" OD

3/8" OD

3/4" OD

1/2" OD

56

NZ049

NAH060

3/4" OD

3/8" OD

7/8" OD

3/8" OD

7/8" OD

1/2" OD

90

NZ064

NAH060

7/8" OD

1/2" OD

7/8" OD

1/2" OD

1-1/8" OD

1/2" OD

92

NZ072

NAH060

7/8" OD

1/2" OD

7/8" OD

1/2" OD

1-1/8" OD

1/2" OD

104

Notes: Lineset charge for R410A is 0.50 oz. per ft. for 3/8" and 1.0 oz. per ft. for 1/2" tube.

Rev.: 6/8/07

Initial Total System Charge = Factory Envision Split charge + lineset charge + 20 oz, then adjust charge by subcooling and superheat measurements.

20 feet

40 feet

60 feet