Unit operating parameters, Single speed models – Envision Peripherals Geothermal Indoor Split Heat Pumps User Manual

Page 26

background image

26

ENVISION SERIES INSTALLATION MANUAL

Single Speed Models

Unit Operating Parameters

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

Superheat Subcooling

Water Temp

Rise °F

Air Temp

Drop °F DB

1.5

120 - 142

215 - 240

7 - 15

7 - 14

18 - 22

18 - 22

3.0

115 - 138

190 - 225

10 - 18

4 - 11

8 - 10

18 - 22

1.5

125 - 148

290 - 315

8 - 14

6 -11

18 - 22

18 - 22

3.0

123 - 146

255 - 290

9 - 15

5 - 10

8 - 10

18 - 22

1.5

134 - 157

340 - 380

8 - 14

6 - 13

18 - 22

16 - 20

3.0

130 - 155

310 - 350

9 - 15

5 - 12

8 - 10

16 - 20

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

Superheat Subcooling

Water Temp

Drop °F

Air Temp

Rise °F DB

1.5

69 - 81

254 - 334

7 - 13

5 - 13

7 -10

18 - 24

3.0

75 - 87

260 - 340

7 - 14

5 - 13

3 - 6

20 - 26

1.5

98 - 113

293 - 373

7 - 14

7 - 15

8 - 11

20 - 26

3.0

105 - 120

300 - 380

7 - 15

7 - 15

4 - 7

22 - 28

1.5

133 - 150

315 - 415

9 - 15

9 - 16

11 - 14

26 - 32

3.0

139 - 157

325 - 425

9 - 15

9 - 16

7 - 10

28 - 34

Entering Water

Temp °F

Water Flow

GPM/Ton

Cooling -- No Desuperheater

50

70

90

Entering Water

Temp °F

Water Flow

GPM/Ton

Heating -- No Desuperheater

30

50

70

Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.
Heating performance based on entering air temperature of 70º F DB.