beautypg.com

Emerson TRANSMITTER 3350 User Manual

Page 21

background image

20

Connect the Model 3350/3700 to a power supply as follows:

1. Use 18 to 12 AWG (0,75 to 4,0 mm

2

) wire.

2. Using a flat-head screwdriver, loosen the captive screws that secure

the display cover to the housing.

3. Ground the transmitter as follows:

Connect the ground wire to the green screw (power supply
ground; see Figure 11).

Connect the power supply ground wire directly to earth ground.

Keep all ground leads as short as possible.

Ground wiring must have less than 1 ohm impedance.

4. Connect wires to terminals 9 and 10 on the gray terminal block (see

Figures 11 and 12).

5. Close the display cover and tighten the screws.

6. A user-supplied switch may be installed in the power supply line. For

compliance with low-voltage directive 73/23/EEC (European
installations), a switch in close proximity to the Model 3350/3700 is
required.