6.3

Unpacking

Carefully remove bolts and protective shipping hood. See

Figure 3. Remove the bolts holding modules to shipping

pallet. Also remove hardware bolting upper channels of

modules together. Do not remove modules at this time.

Base supports for horizontally stacked modules are more

easily attached before removing modules from pallet (see

Section 8 System Assembly).

Note: Placement of modules on shipping pallet has

no relationship to final installation and should be

disregarded.

UNPACKING MODULES

Figure 3

6.4

Handling of Modules

The design of the modular tray permits handling by a fork

lift, portable crane or by a hoist sling . Whichever method

is used, make sure equipment can safely handle the mod-

ule weight. See Section 6.2 for module weights.

Always use the two lifting straps and four lifting shackles

for lifting and placement of modules. See Figure 4.

HANDLING - LIFTING STRAP PLACEMENT

Figure 4

NOTE (for Figure 4):

1) Straps must be criss-crossed.

2) Observe lifting shackle orientation

and proper channel hole use.

3) See Figure 13 for handling modules in horizontal

orientation.

4) Never lift more than one module with straps and

hooks.

HANDLING MODULE

Figure 5

SECTION 7: SYSTEM ARRANGEMENTS

7.0

Module Arrangements

Absolyte GX batteries may only be arranged horizontally.

Figure 6 shows some typical arrangements.

TYPICAL SYSTEM ARRANGEMENTS

Figure 6

Modules are shipped without connectors installed. The

wiring diagram enclosed with shipment will show proper

battery hook-up. Module stack height limitation depends on

cell size and the seismic requirements of the application.

SECTION 8: SYSTEM ASSEMBLY

8.0

Module Assembly Identification

Consult layout/wiring diagram for total number and type

of module assemblies in system. Compare required

module assemblies called for on layout/wiring diagram

with modules in shipment for completeness before

continuing further.

The Absolyte GX has a standard module configuration of

two cells per module. Where application voltage requires,

Absolyte GX

3 Stacks

4 High

End to End

Absolyte GX

2 Stacks

6 High

Back to Back