Intermittent pilot operating instructions, Figure 44 – Empire Comfort Systems DVF-42-2 User Manual

Page 26

background image

Page 26

R-5627

Intermittent Pilot Operating Instructions

The intermittent pilot (120/24 volt system) is ON when the main burner
is ON. When the main burner is OFF the intermittent pilot is OFF.

IP-Model Pilot (Figure 44)
This fireplace is using a Honeywell "Smart Valve" system for intermittent
pilot ignition.

On a call for flame the control turns on a 24 volt mini hot surface ignitor
which lights a pilot that in turn lights the main burner.

Pilot Flame Adjustment (Figure 45)
The pilot flame should envelop 3/8 to 1/2 inch (10 to 13mm) of the tip
of the flame rod. (See Figure 44)

To adjust:

1. Remove the pilot adjustment cover screw.
2. Turn the inner adjustment screw clockwise

to decrease

or counterclockwise

to increase pilot flame. Pilot adjust-

ment is shipped at full flow rate. Turn the inner adjustment screw
clockwise

if the inlet pressure is too high.

3. Replace the cover screw after the adjustment to prevent gas

leakage.

BURNER

PILOT

HOT SURFACE
IGNITOR

FLAME
ROD

GROUND
ELECTRODE

3/8" TO 1/2"
PILOT FLAME

IP-MODEL PILOT

Figure 44

ON

OFF

IGNITOR

C

ONTROL

INLET PRESSURE TAP

OUTLET PRESSURE TAP

PILOT ADJUSTMENT-
UNDER CAP SCREW

PILOT OUTLET

PRESSURE REGULATOR
ADJUSTMENT-UNDER CAP
SCREW

GAS FLOW

IGNITOR

C

ONTROL

TO 24 V. THERMOSTAT

TO 24 V. COMMON ON TRANSFORMER

TO 24 V."HOT" ON TRANSFORMER

WIRING

I P-MODEL GAS VALVE AND WIRING

IGNITOR-PILOT ASSY.

Figure 45

Intermittent Pilot Wiring Diagram (Figure 46)