Figure 20 and Chart 1 lists examples of possible venting systems using
one (1) 90

°

elbow. Eight (8) feet is listed as maximum vertical vent run

with 20 feet of maximum horizontal vent run. Vertical dimensions are
based on centerline to centerline of pipe. Horizontal dimensions are
based on centerline of pipe to end of termination.

SEE CHART FOR PERMISSIBLE "H" AND "V" DIMENSIONS

SEE CHART FOR PERMISSIBLE "H" AND "V" DIMENSIONS

Figure 20

CHART 1 (Figures 21, 22 and 23)
Venting with One (1) 90

°

Elbow or Two (2) 90

°

Elbows

Total Vertical

Total Horizontal

(With Fire Box) V

H

1

or H

1

+ H

2

4.5' minimum

3' maximum

4.5' minimum

4' maximum

5' minimum

8' maximum

6' minimum

12' maximum

7' minimum

15' maximum

8' minimum

20' maximum

25' maximum vertical
20' maximum horizontal run

Figure 21 and Chart 1 list examples of possible venting systems using
two (2) 90

°

elbows. V is listed as minimum vertical dimensions and H1

+ H2 is listed as total of maximum horizontal dimensions. The maximum
vertical and horizontal distances for two (2) 90

°

elbows as shown in

Figure 21 are 20 feet.

Attention: Refer to Figure 8 for additional venting requirements.

SEE CHART FOR PERMISSIBLE "H" AND "V" DIMENSIONS

NOTE: H1 AND H2 MUST BE ADDED TOGETHER TO USE CHART