MULTI-ZONE CONDENSER SEQUENCE OF OPERATION

EMI America Series multi-zone heat pump

condensers are designed to operate with

EMI America Series indoor air handlers.

Both the condenser (outdoor unit) and

evaporator (indoor unit) have a high Volt

service connection. Each is to be indepen-

dently connected to the electrical service

panel. (See the unit name plate for the cor-

rect breaker type and size). The outdoor

and indoor units are also connected to each

other through a low Volt interconnect wiring.

A 24V transformer located in the indoor unit

provides the low Volt power source.

The S & T series (S2HA, T2HA, T3HA &

T4HA) is a limited range heat pumps that

will provide comfort cooling or heat pump

operation operate at an outdoor tempera-

ture range between 35°F and 115°F for

cooling, 35°F and 75°F for (heat pump)

heating. The outdoor unit is equipped

with a thermostat that will switch off the

condenser when temperature falls below

35°F. For heat pump mode the condenser

operation will cease and then switch on

the indoor electric heat. For cooling mode,

condenser operation will cease.

The S & T series (S2HA, T2HA, T3HA &

T4HA) limited range heat pump condens-

ers are designed to operate as a single

stage cooling, two stage heating unit. For

full operation the unit should be matched

with an appropriate EMI indoor unit with

electric heat and unit mounted controls or

a wall mounted thermostat.

For two stage heating operation the indoor

unit must be equipped with an electric strip

heater.

See the instruction manual for the indoor

unit on the selection of the proper thermo-

stat for the system.

Condenser Operation:

The transformer located in the indoor unit

provides 24V, low-Volt control power to the

condenser (outdoor unit). This can be mea-

sured across low-Volt terminals “R” and “C”.

Heat pump condensers utilize a reversing

valve to provide reverse cycle operation.

Therefore the outdoor unit will act as ei-

ther a condenser or an evaporator there-

by providing comfort cooling or heating to

the indoor space. The reversing valve is

energized in cooling. Should the valve fail

to actuate, the system will default to the

heating mode of operation.

Cooling operation, Multi-zone Heat

Pump:

Cooling mode operation requires that the

control (either unit mount or remote wall

mount thermostat) make a connection be-

tween low-Volt terminals “R” and “Y” along

with “R” and “O”. When the indoor control

is placed in cooling mode, with the set point

temperature below the room temperature,

the reversing valve will energize (R & O)

along with the compressor and outdoor fan

(R & Y). When the indoor control is satis

-

fied and the room temperature falls below

the set temperature, the compressor and

fan will de-energize. The EMI indoor unit

is equipped with an anti-short cycle timer

(ASCT) will prevent the compressor from

re-starting for three minutes.

When the outdoor temperature falls below

35°F, compressor operation will cease.

Heating operation, Multi-zone Heat

Pump:

Heating mode operation requires that the

control (either unit mount or remote wall

mount thermostat) make a connection

between low-Volt terminals “R” and “Y”

only. When the indoor control is placed

in heating mode, with the set point tem-

perature above room temperature, the

compressor and outdoor fan (R & Y) will

energize. When the indoor control is satis-

fied and the room temperature rises above

the set temperature, the compressor and

fan will de-energize. The EMI indoor unit

is equipped with an anti-short cycle timer

(ASCT) will prevent the compressor from

re-starting for three minutes.