beautypg.com

EMI S1H2D User Manual

Emi eng in ee r ing submit tal

background image

Rome, New York, USA

Enviromaster International LLC

1

emi

eNG

iN

ee

R

iNG Submit

tal

JOB NAME: _____________________________________ LOCATION: _______________________________________

PURCHASER: _____________________________________________________________________________________

ENGINEER: _______________________________________________________________________________________

SUBMITTED TO: _________________________________ FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ]

SUBMITTED BY: _________________________________ DATE:____________________________________________

UNIT DESIGNATION: SCHEDULE #: _______________ MODEL #: ________________________________________

WlH12-S1H2000_101

Single-Zone Cooling / Heat Pump

Rev. A [05/08]

WLH12 ELECTRICAL SPECIFICATIONS

V

olts/

HZ/PH

Fan RLA

Heater

K.W

.

Amps

T

otal

Amps

Min. V

olt

M.C.A.

HACR

BRKR

115/60/1

0.64

0.64

104

0.8

15

115/60/1

0.64

.75

6.5

7.14

104

8.9

15

208/230/60/1

0.34

0.34

197

0.4

15

208/230/60/1

0.34

3

13.04

13.38

197

16.7

20

HEAT PUMPS SYSTEM OPTIONS WITH WLH12/S1H2

Cooling

Btuh

Heating

Btuh

SEER HSPF

SHR

EER

COP

11,400

10,600

13.0

8.0

.73

11.5

3.4

WLH

S1H

CapaCities:

Cooling .................... 11,400 Btuh
Heating (High) ........ 10,600 Btuh
Heating (Low)........... 6,200

Btuh

indoor Design temp °F DB/WB
Cooling .............................. 80/67
Heating.............................. 70/57

Outdoor Design temp °F DB/WB
Cooling .................................95/75
Heating (High) ......................47/43
Heating (Low).......................17/15

S1H ELECTRICAL SPECIFICATIONS

Model

Volts/HZ/PH

Total

Amps

Min

Volt

M.C.A.

HACR
BRKR

S1H2A

115/60/1

10

104

12.2

20

S1H2D

208/230/60/1

5.1

197

6.2

15

stanDarD Features:

evaporator – High Wall mounted:

• Universal unit mounted, infrared compatible control

package, configurable to either unit mount or optional

wall thermostat operation.

• Compatible with most standard wall mounted, 24V

thermostats

• Motorized supply louver

• Integral field condensate pump connector

• Condensate pan over flow protection

• Anti-short cycle compressor protection

• Indoor coil freeze protection

• Dry mode for humidity control (optional electric heat

required)

• Memory back up for auto re-start following power

outage

• Fan purge

stanDarD Features:

Condenser – Side Discharge / vertically arranged:

• R-22 refrigerant

• Factory installed Low Ambient cooling to 32°F

• Duratec compressor protection package

- Suction Accumulator

- Filter dryer

- High pressure switch (manual reset)

- Thermostatically controlled crankcase heater

- Start assist

• Coated wire coils and fan guards

• Five year compressor / one year parts warranty

Thermostatically controlled crankcase heater – This feature
energizes the crankcase heater only when needed, removes
the heater from the electrical circuit at conditions where
it’s not required, saving unnecessary Watts, and increasing

overall system efficiency.

This manual is related to the following products: