beautypg.com

Start-up, Trouble shooting, Main valve – Jordan Valve Mark 695 Series - Piloted Tank Blanketing Regulator User Manual

Page 2

background image

NEVER reduce the pipe size on the valve outlet to the

tank. This line must always be as large as the valve

size, or one pipe size larger to assure it does not act

as a restriction.

Any downstream isolation valve after the regulator

must be a full port type. The isolation valve cannot

act as a restriction.

The sensing line must be a minimum of 3/8” tube.

A sensing line isolation valve is recommended Again,

must be full ported.

Slope the sensing line to the sensing port on the

tank.

Keep the sensing line as short and straight as

possible.

For each 10 feet of sensing line, increase the tube by

1/8”. (Especially important on the blanket pressures

of less than 5 inches of water column).

Keep the sensing port on the tank as far removed as

possible from the downstream pipe outlet going into

the tank.

Start-Up

With the inlet, and bypass shutoff valves closed,

and no pressure in the downstream line:

1. Slowly open the inlet valve just enough to start

flow through the valve. Observe the tank pressure

gauge. Increase the downstream pressure slowly by

gradually opening the inlet valve.

2. Do not fully open the inlet valve until you are sure that

the regulator has control of the system. Usually, the

handwheel on the inlet valve will turn freely when this

is achieved.

3. To change the controlled pressure, adjust the set

screw (25), and secure with the jam nut (26), and the

closing cap (12).

Trouble Shooting

The first step in troubleshooting a piloted pressure

regulator is to classify the action of the controlled

pressure into one of the following categories:

A. Under Pressure: Controlled pressure too low; not

enough flow or no flow through valve.

B. Over Pressure: Valve will not close or controlled

pressure increases after valve closes.

C. Pressure Fluctuates: Controlled pressure rises and

falls, will not settle out under low loads.

The next step is to determine what could cause the

trouble. The third step is to locate and remedy the cause

by the process of elimination. Make no assumptions and

check the easy ones first. The guide below lists the

controlled pressure action, common causes and

procedure for checking each cause.

Controlled pressure action UNDER PRESSURE:

Valve undersized for application. Check capacity

required and valve capacity. As described in API-

2000.

Line strainer screen clogged. Blow down strainers or

visually check that they are clear.

Incorrect setting on range spring. Vary the setting

and check response.

Main valve diaphragm or balance diaphragm

ruptured. See section on valve maintenance.

Malfunction of other piping components. Check

for leaking safety valves, inadvertently opened or

closed valves.

Controlled pressure action OVER PRESSURE:

Incorrect setting on range spring. Vary the setting

and check response.

Main valve seats leaking. Close inlet shut-off valve,

allow downstream pressure to bleed off, close outlet

valve and remove loading pressure tubing. Back out

adjusting screw on valve until free. Crack open inlet

shut-off valve - if the fluid issues from the main valve

port, the main valve seats are leaking.

By-pass shut-off leaking. During period of leakage

close outlet shut-off valve, observe downstream

pressure gauge

Under certain circumstances, the vent valve may be

open when the tank is not being filled. This may not

be caused by an inability to control or seat leakage.

The tank may be “outbreathing” due to increases

in the temperature of the gas or contents inside the

tank.

Controlled Pressure Fluctuates:

Valve oversized. Check capacity required and valve

capacity per API 2000.

Main Valve

Note: All work to the main valve can be accomplished
in-line. The only reason to remove the valve is if
the location makes it too difficult to work on the
regulator.

Mark 695 Series Tank Blanketing Valve

-2-