C.

MAIN VALVE OPEN AND CLOSES, BUT

DOES NOT CONTROL DOWNSTREAM

PRESSURE:

1.

If pressure remains too high despite adjustment

of the pressure-reducing pilot, refer to

MAIN VALVE FAILS TO CLOSE, above.

2.

If pressure remains too low despite adjustment

of the pressure-reducing pilot, refer to MAIN

VALVE FAILS TO OPEN, above.

3.

If pressure oscillates, you may likely be in a

period of very low demand. Frequently this

problem will disappear as demand increases.

In the meantime, further closing of the flow

control valve may help damp out the oscillations.

In an extreme case, try adjusting the

pressure slightly higher.

D. MAIN VALVE OPENS AND CLOSES BUT
DOES NOT SUSTAIN UPSTREAM PRESSURE.

1.

Pressure-sustaining pilot adjusted too far coun-

terclockwise. See Adjustment instructions.

2.

Stem of pressure-sustaining pilot binding or

seat deteriorated. Disassemble pilot and deter-

mine cause.