7. ErrorID’s
ErrorID
Description
Details
0-4099
5000+
[TwinCAT-specific]
See the Beckhoff Information System, section “ADS Return
Codes” for details.
4100
Vendor ID mismatch
Product not compatible. This FB is only for Vendor ID
0x00000539 (Yaskawa).
4101
Product Code mismatch
Product not compatible. This FB is only for Product codes
0x02200001 (Sigma-5 Rotary) and 0x02200002 (Sigma-5
Linear). If using Sigma-5 CoE Drive, get latest FB from
Yaskawa.com.
4102 Version
mismatch
Product not compatible. This FB is only for certain EtherCAT
revisions. If using Sigma-5 CoE Drive, get latest FB from
Yaskawa.com, or, see Section 9, “Modifying Function Blocks.”
4103
Object not found
Error reading object data type or data type not supported.
4104
File corrupt
File is corrupt. Store the parameters again.
4105
File ID is 0
No version of the ID of file was read. Possibly incorrect file, or
FB has an error.
4106
File ID mismatch
This file was made with a different version than this Function
Block. Obtain the latest FB from Yaskawa.com
4107
Incorrect FSA state
Not in FSA state "Switch On Disabled". StatusWord expected
as x1xx_0000 (bin). See following notes.
4108
Incorrect Device state
Drive not set to PRE-OP mode. Set the drive to PRE-OP mode
before using this FB. See following notes.
4109
File exists already
When trying to store parameters to a file, that file currently
exists. A new file name or location must be provided.
4110
Servo state incorrect
Servo must be off. StatusWord cannot be x00x_0111,
xx1x_x011_0111, or x0xx_1111 (bin).
4111
Adjusting Status
incorrect
Adjusting status must be 1, 2, 3, or 255, but read as a different
value.
4112
Internal Function Block
Error
Function block internal programming error - Function Block State
Not Found.
4113
Adjusting & Abort
commands failed
Adjusting command failed, so Abort (Step 4) was performed.
But Abort also failed (Status of Adjusting = 2).
4114
Adjusting & Abort
commands failed
Adjusting command failed, so Abort (Step 4) was performed.
But Abort also failed (Status of Adjusting = 2). Reply data for
the Adjusting command failure exists in object 0x2710:03.
4115
Send Request 1008
failed
Error occurred (Status of Adjusting = 2) while performing Send
Request 1008 (Step 1). No reply exists.
4116
Send Request 1008
failed
Error occurred (Status of Adjusting = 3) while performing Send
Request 1008 (Step 1). Reply exists in object 0x2710:03.
4117
Send Preparation failed
Error occurred (Status of Adjusting = 2) while performing Send
Preparation (Step 2). No reply exists.
4118
Send Preparation failed
Error occurred (Status of Adjusting = 3) while performing Send
Preparation (Step 2). Reply exists in object 0x2710:03.