Yaskawa CM092 User Manual
Page 40
EtherNet/IP 3-11
Yaskawa Extended Speed/Torque Input Instance 155 (9Bh)
(Details for bytes 10 through 23, Error Alarm Signals 1, 2, and 3)
Bytes 18 (Low) and 19 (High) -
Error Alarm Signal 1
Bytes 20 (Low) and 21 (High) -
Error Alarm Signal 2
Bytes 22 (Low) and 23 (High) -
Error Alarm Signal 3
Bit
Fault
Bit
Fault
Bit
Fault
0h
PUF DC Bus Fuse Open
0h
EF3 External Fault - Terminal S3
0h
CE
Modbus Communication Error
1h
UV1 DC Bus Undervoltage
1h
EF4 External Fault - Terminal S4
1h
BUS Bus Fault
2h
UV2 Control Circuit Undervoltage
2h
EF5 External Fault - Terminal S5
2h
Not Used
3h
UV3 Main Circuit Contactor
Answerback Fault
3h
EF6 External Fault - Terminal S6
3h
Not Used
4h
Not Used
4h
EF7 External Fault - Terminal S7
4h
CF
Out of Control Fault
No Determination of Motor Speed
5h
GF Ground
Fault
5h
EF8 External Fault - Terminal S8
(F7U/G7U Only)
5h
SVE Zero
Servo
Fault
(F7U, G7U and G5M in Closed-loop
flux vector mode (FVC) only)
6h
OC Overcurrent
Fault
6h
FAN Drive Cooling Fan Fault
(models with internal cooling fans
only)
6h
EF0 External Communications Fault
7h
OV Overvoltage Fault
7h
OS
Overspeed Fault
7h
Not Used
8h
OH Heatsink
Over
temperature
Fault
8h
DEV Speed Deviation Fault
8h
Not Used
9h
OH1 Drive Overheat Fault
9h
PGO PG Open, Encoder
(Pulse Generator open circuit)
9h
Not Used
Ah
OL1 Motor Overload Fault
Ah
PF
Input Phase Loss Fault
Ah
Not Used
Bh
OL2 Drive Overload Fault
Bh
LF
Output Phase Loss
Bh
EF9 External Fault - Terminal S9 (G7U)
Ch
OL3 Overtorque Fault 1 (L6-02)
Ch
Not Used
Ch
EF10 External Fault - Terminal S10 (G7U)
Dh
OL4 Overtorque Fault 2 (L6-05)
Dh
OPR Operator Disconnected
Dh
EF11 External Fault - Terminal S11 (G7U)
Eh
RR Dynamic
Braking
Transistor
Failure
Eh
ERR Eprom R/W Error
Eh
EF12 External Fault - Terminal S12 (G7U)
Fh
RH Dynamic
Braking
Resistor
Overheat
Fh
Not Used
Fh
CPF Control Circuit Fault/Peripheral Fault