SMA SB 4200TL Multi-String Installation User Manual

Page 21

background image

SMA

Technologie AG

Installation

Installation Guide

SB4200TL-13:SE2006

Page 21

Connection of AC output

Please follow the steps below:

1.

Check the grid voltage. If it is above 260 V
(German standard), the Sunny Boy 4200TL
Multi-String stops operation. The local public
utility company should solve this problem.

max. 260 V!

The maximum grid voltage for feeding

operation is 260 V!

2.

Disconnect the grid (switch off the circuit break-
er), secure it against accidental reactivation and
ensure that it is disconnected.

Before opening the Sunny Boy 4200TL

Multi-String check whether the AC

output is safely isolated from supply!

3.

Unscrew the lid from the enclosure of the Sunny
Boy 4200TL Multi-String and carefully remove
the lid. Then pull the PE cable off the inside of
the lid.

Make sure that you pull off the green

yellow PE cable from the inside of the

Sunny Boy when you open it!

4.

Connect the AC cable as illustrated in the figure
on the side. Use the cable gland that is included
in the delivery of your Sunny Boy 4200TL Multi-
String. Phase (L) and Neutral (N) may not be
mixed up.

Connection of „L“ and „N“

1.

2.

3.

Off!

Photovoltaik-Stringwechselrichter
Photovoltaic

string

inver

ter

L

N