Requirements for the Installation

SMA

Technologie AG

Page 14

SB4200TL-13:SE2006

Installation Guide

Important for the selection of the location:

Make sure there is a sufficient space for heat dissipation! In a normal environment
the following clearances should be provided for the Sunny Boy 4200TL Multi-String:

In a living area the Sunny Boy 4200TL Multi-String
should not be mounted on plaster panels etc. in order
to avoid noises.

We recommend to install the inverter on a firm and
sturdy surface.

The Sunny Boy 4200TL Multi-String will emit a slight
noise during operation. This noise can be annoying
when the Sunny Boy is installed within a living area.

Unintended removal of the PV plug connectors can damage the
connectors and even result in serious injuries. Install the Sunny Boy
4200TL Multi-String at a place where an unintended removal of the
PV plug connectors (e. g. by children) is not possible.

Some parts of the Sunny Boy can reach temperatures over 60 °C.

Do not install the Sunny Boy on flammable construction materials,
in areas where highly inflammable materials are stored or in po-
tentially explosive environments!

Minimum clearances

Lateral

20 cm

Top

20 cm

Bottom

20 cm

Front

5 cm

20 cm

20 cm

20
cm

20
cm

5

cm

Photovoltaik-Stringwechselrichter
Photovoltaic string inverter