SB5000TL-12:SE2006

Page 31

7.4 Sunny Boy 5000TL Operating Parameters

Any unauthorized modifications of the operating parameters can
• result in serious injuries or casualties due to altered internal

safety precautions within the Sunny Boy

• void the operating permission of the Sunny Boy
• void the warranty of the Sunny Boy

Never change the operating parameters with out explicit permis-
sion and instructions!

Name

Unit

Range

Default

Betriebsart/
Operating Mode

MPP/

Ikonst/

UKonst/

Stop

MPP

Default

GER/ENS

dFac-MAX

Hz/s

0.005 ... 4.0

0.25

dZac-MAX

mOhm

0 ... 2000

350

E_Total

kWh

0 ... 200000

Fac-Delta-

Hz

0 ... 4.5 (0.19)

0.19

Fac-Delta+

Hz

0 ... 4.5

0.19

h_Total

h

0 ... 200000

Inst.-Code

NiTest/
impedance test

0 / 1

1

Riso-Min

kOhm

1000 ... 30000

1000

Speicherfunktion/
Memory Function

none

Speicher/
Storage

permanent/

volatile

permanent

Uac-Max/
Vac-Max

V

180 ... 300

261

Uac-Min/
Vac-Min

V

180 ... 300

198

Usoll-Konst A/
Vconst-SetpointA

V

0 ... 750

290

Usoll-Konst B/
Vconst-SetpointB

V

0 ... 750

290

Usoll-Konst C/
Vconst-SetpointC

V

0 ... 750

290