SB5000TL-12:SE2006
Page 29
7 Technical Documentation
7.1 Data PV Generator Connection
7.2 Data Grid Connection
Max. input open-circuit voltage
U
PV 0
750 V (at -10 °C Module Temperature)
Input voltage, MPP operation
U
PV
125 V ... 750 V DC
Max. input current
I
PV m ax
7,5 A per input port
Max. input power
P
PV
3800 W per String
Recommended generator power
6600 Wp
All-pole disconnector
on DC input side
DC plug connector standard - other snap
cable connectors optional
Surge voltage protection
thermally monitored varistors
Voltage ripple
U
PP
< 10 % of input voltage
Personnel protection
Ground Fault monitoring (Riso > 1 MΩ)
Internal consumption in operation
< 10 W (stand-by)
Pole confusion prevention
by short-circuit diode
Nominal output power
P
AC nom
4600 VA
Peak output power
P
AC m ax
5100 W
Nominal output current
I
AC N enn
20 A
Harmonic distortion of output
(with K
U nom
< 2 %, P
AC
> 0,5 P
AC n-
om
)
THD
IAC
< 4 %
Short-circuit resistance
Imax = 30 A
Operating range, grid voltage
U
AC
198 ... 260 V AC
Operating range, grid frequency f
AC
49.8 ... 50.2 Hz
All-pole disconnector on grid side
independent disconnection device
(MSD), (2 independant systems)
Phase difference
(related to basic wave of current)
cos Phi 1
Overvoltage category
III
Test voltage (50 Hz)
1.65 kV (5 s unit / type test)
Surge voltage test
4 kV (1.2/50 ms)
(serial interface: 6 kV)
Internal consumption in stand-by
0.25 W