beautypg.com

7 technical documentation, 1 data pv generator connection, 2 data grid connection – SMA SB 5000TL Multi-String Installation User Manual

Page 29: Technical documentation, Data pv generator connection, Data grid connection

background image

SMA

Technologie AG

Technical Documentation

Installation Guide

SB5000TL-12:SE2006

Page 29

7 Technical Documentation

7.1 Data PV Generator Connection

7.2 Data Grid Connection

Max. input open-circuit voltage

U

PV 0

750 V (at -10 °C Module Temperature)

Input voltage, MPP operation

U

PV

125 V ... 750 V DC

Max. input current

I

PV m ax

7,5 A per input port

Max. input power

P

PV

3800 W per String

Recommended generator power

6600 Wp

All-pole disconnector
on DC input side

DC plug connector standard - other snap
cable connectors optional

Surge voltage protection

thermally monitored varistors

Voltage ripple

U

PP

< 10 % of input voltage

Personnel protection

Ground Fault monitoring (Riso > 1 MΩ)

Internal consumption in operation

< 10 W (stand-by)

Pole confusion prevention

by short-circuit diode

Nominal output power

P

AC nom

4600 VA

Peak output power

P

AC m ax

5100 W

Nominal output current

I

AC N enn

20 A

Harmonic distortion of output
(with K

U nom

< 2 %, P

AC

> 0,5 P

AC n-

om

)

THD

IAC

< 4 %

Short-circuit resistance

Imax = 30 A

Operating range, grid voltage

U

AC

198 ... 260 V AC

Operating range, grid frequency f

AC

49.8 ... 50.2 Hz

All-pole disconnector on grid side

independent disconnection device
(MSD), (2 independant systems)

Phase difference
(related to basic wave of current)

cos Phi 1

Overvoltage category

III

Test voltage (50 Hz)

1.65 kV (5 s unit / type test)

Surge voltage test

4 kV (1.2/50 ms)
(serial interface: 6 kV)

Internal consumption in stand-by