5  Connection

SMA Solar Technology AG

14

485i-Module-IA-en-18

Installation Manual

6. Insert the 485 Data Module and slide the ribbon

cable upwards behind the display. The key on the
top edge of the 485 Data Module must fit into the
hole in the plastic retainer in the inverter.

7. Fasten the 485 Data Module hand-tight with the

hexagon socket screw (AF 3, torque: 1,5 Nm).

8. Flip down the display.
9. Plug the ribbon cable plug onto the centre

connector strip.

5.3 Connecting the 485 Data Module

To achieve a good signal quality, observe the cable recommendation (see technical description
"RS 485 Cabling Plan")

During operation, AC cables generate an electromagnetic field which may induce interference
in plant communication.

Disturbance of Data Transmission due to AC Cables

• Lay the RS485 communication cables using suitable fastening material and with a

minimum clearance of 50 mm to the AC cables.