SMA SUNNY BOY User Manual
Page 36
Measurement Channels and Messages
SMA Solar Technology AG
36
SB_SMC-BEN092840
User Manual
Imax
Overcurrent on the AC side. This fault code is displayed if the current in
the AC grid is greater than specified.
Corrective measures
• Please contact your installer to have the plant configuration and the
grid conditions checked.
Imax DC
Overcurrent on the DC input side of the Sunny Boy Multi-String. A current
exceeding the maximum permissible value has been detected at the input
of the inverter.
Corrective measures
• Please contact your installer to have the plant configuration
checked.
K1-Close
K1-Open
K2-Open
Fault during relay test.
Corrective measures
• Please contact your installer or the SMA Solar Technology
Serviceline when this problem occurs several times in succession.
Kom DC-BFS
Internal communication fault.
Corrective measures
• Please contact your installer or the SMA Solar Technology
Serviceline if this problem recurs.
L<->N
L and N are swapped on the AC connection.
Corrective measures
• Please contact your installer to have the plant checked over.
L-Netz
L-WR
N-Netz
N-WR
A grid relay is faulty. The inverter checks the relays connecting it to the
grid before feeding power into the grid. If the grid relays do not function
properly, the inverter does not connect to the grid for safety reasons.
Corrective measures
• If this fault message is displayed repeatedly, it means that inverter
operation is permanently disabled. If the inverter is equipped with
a communication interface, the installer can try to rectify the fault
with the help of a communication product.
• Should this be unsuccessful, please contact the SMA Solar
Technology Serviceline.