3.2 Perform Software Update (Single Inverter)
Procedure
1. Connect the PC to the inverter
2. Open an internet browser (Internet Explorer or Firefox).
3. Type the inverter IP address in the address field.
To find the IP address go to [Setup Communication Setup IP Setup] in the
display.
4. On the Web Server welcome page, enter the login.
Comprising user name and password.
5. Go to [Plant Setup Plant details]
6. Click on the ‘Browse’ button to navigate to the location of the extracted .dcf file.
7. Select the file
8. Click on the 'Start update' button and confirm the update.
9. Do not press any buttons on the inverter display or the PC while the update is in progress.
The inverter will restart and return to the welcome page.
10. If you need to change the GridCode settings a level 2 password is required.
11. Go to [Setup → Inverter details → Regional settings].
12. Select [Country →SAVE]. Wait for the webpage to refresh, then different Gridcodes can be
chosen.
13. Select [Grid → SAVE]. You can select [Show Grid List] to get additional information for each
GridCode.
3.3 Perform Software Update (Network with Master)
Procedure:
1. Connect the PC to the master inverter in the network of inverters.
2. Open an internet browser (Internet Explorer or Firefox).
3. Type the inverter IP address in the address field
To find the IP address go to [Setup → Communication → Ethernet] in the display.
Alternatively, type “masterinverter” in the internet browser address field.
4. On the Web Server welcome page, enter your login (comprising user name and password).