beautypg.com

Selected sis commands, Establishing a network (ethernet) connection, Connection timeouts – Extron Electronics MPX Plus 866 A Rev. A User Manual

Page 15: Number of connections, Verbose mode, Host-to-switcher instructions, Selected sis commands, Establishing a network (ethernet) connection -2, Remote control

background image

4-2

Refer also to the MPX Plus 866 A User’s Manual at www.extron.com.

Refer also to the MPX Plus 866 A User’s Manual at www.extron.com.

Selected SIS Commands

The switchers have Simple Instruction Set (SIS

) commands that

you can use for operation and configuration. You can run these

commands from a PC connected to any of the switcher’s three

serial ports or the Ethernet port. See

l

,

m

, and

o

, on pages 2-5,

for connection information.

Establishing a network (Ethernet) connection

Establish a network connection as follows:
1

.

Open a TCP socket to port 23 using the switcher’s IP

address.

N

The factory default IP address is 192.168.254.254.

The switcher responds with a copyright message including

the date, the name of the product, the firmware version,

the part number, and the current date/time.

N

If the switcher is not password-protected, the device is now

ready to accept SIS commands.

If the switcher is password-protected, a

password

prompt appears.

2

.

If the switcher is password-protected, enter the appropriate

password.

If the password is accepted, the switcher responds with

Login User or Login Administrator.

If the password is not accepted, the

Password prompt

reappears.

Connection timeouts

The Ethernet link times out and disconnects after a designated

period of no communications. By default, this timeout value

is set to 5 minutes, but the value can be changed. See the

Configure port timeout SIS commands on page 4-10.

N

Extron recommends leaving the default timeout at

5 minutes and periodically issuing the Query (Q)

command to keep the connection active or disconnecting

the socket and reopening the connection when necessary.

Number of connections

A switcher can have up to 200 simultaneous TCP connections,

including all HTTP sockets and Telnet connections. When

the connection limit is reached, the switcher accepts no new

connections until some have been closed. No error message or

indication is given that the connection limit has been reached.

To maximize performance of your switcher, the number of

connections should stay low and unnecessary open sockets

should be closed.

Verbose mode

Telnet connections to a switcher can be used to monitor

for changes that occur on the switcher, such as front panel

operations and SIS commands from other Telnet sockets or a

serial port. For a Telnet session to receive change notices from

the switcher, the Telnet session must be in verbose mode 3. See

the

Set verbose mode command on page 4-10. In verbose

mode 3, the Telnet socket reports changes in messages that

resemble SIS command responses.

Host-to-switcher instructions

The switcher accepts SIS commands through either serial port.

SIS commands consist of one or more characters per command

field. They do not require any special characters to begin or

end the command character sequence. Each switcher response

to an SIS command ends with a carriage return and a line feed

(CR/LF =

]

), which signals the end of the response character

string. A string is one or more characters.

N

The table that begins on the next page is a partial list

of SIS commands. For a complete listing, refer to the

MPX Plus 866 A User's Manual.

MPX Plus 866 A • Remote Control

Remote Control

MPX Plus 866 A • Remote Control

4-3

This manual is related to the following products: