beautypg.com

Westermo EDW-100 User Manual

Page 21

background image

21

6616-2203

Gateway Client mode
Allows one Modbus client (master) on a serial network to connect to one or more
servers (slaves) on the TCP/IP network.

Setting up the EDW-100 as a Modbus Gateway
Set the EDW-100 application mode to Modbus gateway to enable the gateway
functionality. Serial settings and ip-configuration is shared whit the other application
mode but the rest of the Modbus configuration is done on the specific Modbus
configuration page.
To set up the gateway it is necessary to know details about the TCP and the serial
Modbus network. Please refer to the web tool help page for more configuration details.

Ethernet

Modbus

Slave 5

Modbus TCP

RS-485

Modbus RTU or

Modbus ASCII

Modbus Slave 2

Modbus Client

Modbus Slave 3

Modbus Slave 4

Max total 247 Servers

EDW-100

Modbus gateway

1 Client (Master)

and up to

247 servers

(Slaves)

Modbus

Slave 6