Westermo AD-01 User Manual
Page 15

15
6612-2202
Set up of master ports
set up of the master ports is possible using a sND_uD command, CI = 51 (hex)
with the following data field.
Data field
DIF = 01 (hex) VIF = FD (hex) VIFE = E2 (hex) VIFE = 00 (hex) DATA
Description 8-bit integer
Ext. coding
Cont. signal
Write replace
Port setup
The DATA is coded according the following:
Value
Master RS-232 port
Master M-Bus port
00 (hex)
Inactive
Inactive
01 (hex)
Inactive
Active
02 (hex)
Active
Inactive
03 (hex)
Active
Active
Read out of master ports
Read out of the master ports setting is possible using a REQ_uD2 command.
AD-01 will respond with a RsP_uD, CI=72 (hex) with the following data field.
Data field
DIF = 01 (hex) VIF = FD (hex) VIFE = E2 (hex) DATA
Description 8-bit integer
Ext. coding
Cont. signal
Port setup
The DATA is coded according the following:
Value
Master RS-232 port
Master M-Bus port
00 (hex)
Inactive
Inactive
01 (hex)
Inactive
Active
02 (hex)
Active
Inactive
03 (hex)
Active
Active
Error indication
AD-01 includes possibilities to alert the supervision system of short-circuit or overload
on the M-Bus master interface. Readout of error status can be made using a REQ_uD2
command. AD-01 uses the status field in a RsP_uD answer sequence to alert possible
errors.
The coding of the status field is according to the following:
Value status field
Description
00 (hex)
No error
10 (hex)
Overload / short-circuit of
M-Bus master interface