Dip-switch settings, Before dip-switch settings, S1 primary address s2 data rate functionality – Westermo AD-01 User Manual
Page 11

11
6612-2202
DIP-switch settings
Before DIP-switch settings:
Prevent damage to internal electronics from electrostatic discharges (EsD)
by discharging your body to a grounding point (e.g. use of wrist strap).
NOTE DIP-switch alterations are only effective after a power on.
S2
S1
S1 Primary address
S2 Data rate functionality
ON
1 2 3 4 5 6 7 8
Address bit active ('1')
Autobaud
ON
1 2 3 4 5 6 7 8
Address bit inactive ('0')
Data rate using protocol
The units primary address is set up as a 8-bit binary address (0–255)
s1:1 is the least significant bit, s1:8 is the most significant bit.
Observe that only primary addresses 1–250 is allowed to use according to M-Bus
standard.
Example, address 103 = "01100111" binary = S1: 4, 5, 8 OFF, others ON,
see table on page xxxx
Data rate using protocol means that data rate is set using protocol commands.
Autobaud implies that every incoming packet on slave interfaces is data rate
controlled and data rate is set accordingly.