I/o connection – Westermo RFIR-xxx User Manual
Page 18

18
6641-22810
I/O connection
DO+
DI-
DI+
DO-
Product marking
Direction
Description
Digital in –
Input
Digital in –
Digital in +
Input
Digital in +
Status –
Output
Alarm relay (status) contact
Status +
Output
Alarm relay (status) contact
The Status output is a potential free, opto-isolated normally closed solid-state relay. This can be configured to
monitor various alarm events within the RFIR unit, see WeOS Management Guide. An external load in series
with an external voltage source is required for proper functionality. For voltage/current ratings, see Interface
specification section.
The Digital in is an opto-isolated
digital input which can be used
to monitor external events.
For voltage/current ratings, see
Interface Specification section:
External
Load
Status
V
V
Digital In
+
1
2
3
4
–
IO / Relay output
Connect resistance
30 W
Isolation to
All other
Connection
Detachable screw terminal
Connector size
0.2 – 2.5 mm
2
(AWG 24 – 12)
Maximum voltage/current
60 VDC / 80 mA
IO / Digital input
Voltage levels
Vih > 8V Vil < 5V
Iin = 2.9mA @60V
Isolation to
All other
Connection
Detachable screw terminal
Connector size
0.2 – 2.5 mm
2
(AWG 24 – 12)
Maximum voltage
60 VDC