beautypg.com

Type tests and environmental conditions – Westermo FDV-206-1D-1S User Manual

Page 6

background image

6

6660-2201

Type tests and environmental conditions

Phenomena

Test

Description

Test levels

ESD

EN 61000-4-2

Enclosure contact

± 6 kV

Enclosure air

± 8 kV

RF field AM modulated EN 61000-4-3

Enclosure

20 V/m 80% AM (1 kHz), 80 – 2 700 MHz

Fast transient

EN 61000-4-4

Signal ports

± 2 kV

Power ports

± 2 kV

Surge

EN 61000-4-5

Signal ports unbalanced

± 2 kV line to earth, ± 2 kV line to line

Signal ports balanced

± 2 kV line to earth, ± 1 kV line to line

Power ports

± 2 kV line to earth, ± 2 kV line to line

RF conducted

EN 61000-4-6

Signal ports

10 V 80% AM (1 kHz), 0.15 – 80 MHz

Power ports

10 V 80% AM (1 kHz), 0.15 – 80 MHz

Pulse magnetic field

EN 61000-4-9

Enclosure

300 A/m, 6.4 / 16 µs pulse

Voltage dips and
interruption

EN 61000-4-29

DC power ports

10 & 100 ms, interruption
10 ms, 30% reduction
10 ms, 60% reduction
+20% above & –20% below rated voltage

Radiated emission

EN 55022

Enclosure

Class A

FCC part 15

Class A

Conducted emission

EN 55022

AC power ports

Class B

FCC part 15

AC power ports

Class B

EN 55022

DC power ports

Class B

Dielectric strength

EN 60950

Signal port to other
isolated ports

1.5 kVrms 50 Hz 1 min

Power port to other
isolated ports

3 kVrms 50 Hz 1 min
2 kVrms 50 Hz 1 min (@ rated power <60 V)

Temperature

Operating

–20 to +70ºC

Storage & Transport

–40 to +85ºC

Humidity

Operating

5 to 95% relative humidity

Storage & Transport

5 to 95% relative humidity

Altitude

Operating

2000 m / 70 kPa

Reliability prediction
(MTBF)

MIL-HDBK- 217F

Operating

580 000 hours @ 25°C

Service life

Operating

10 year

Vibration

IEC 60068-2-6

Operating

5 – 20 Hz: 2 m²/s³
20 – 200 Hz: – 3 dB/oct
3 axis = 3 * 30 min

Shock

IEC 60068-2-27

Operating

6 ms 1000 m/s²
6 directions, 3 shocks / direction

Enclosure

UL 94

PC / ABS

Flammability class V-1

Dimension W x H x D

52.5 x 100 x 101 mm

Weight

0.6 kg

Degree of protection

IEC 529

Enclosure

IP 40

Cooling

Convection

Mounting

Horizontal on 35 mm DIN-rail