beautypg.com

Watson-Marlow 900 Series User Manual

Page 6

background image

Page

6

Electrical connection

In order to effectively protect the motor from overloads, appropriate motor

protection devices must be used. Motors fitted to the Watson-Marlow series of

pumps are manufactured with a motor temperature cut-out, but a current

overload relay should also be fitted to a contact breaker.
The motor should be connected by a qualified engineer who is

conversant with the appropriate regulations and they should ensure that

the voltage and frequency of the electrical supply corresponds with the

data on the motor plate.
Connect the motor in accordance with the wiring diagram which will be found

in the motor terminal box.
When a motor thermal protection switch is fitted in the motor, the leads will be

found in the motor terminal box. They should be connected to stop the pump if

the switch operates. The switch will open circuit at an over temperature

condition.

The diagram below shows the connection of the drive motor showing possible

ancillary switches and protections. It depends on the installation whether a

reversing switch and interlock with other equipment is included.

Care must be taken to ensure that

the motor terminal links are in the

correct position and that all

connections including the earth

connection are positioned

correctly and securely.
Ingress protection standard will be

compromised if the connection

box cover is not properly replaced

or if the cable gland is not

correctly fitted. Exd motors must

be connected with approved fitting

and practice.
All pumps, excluding those

intended for use in hazardous

atmospheres, may be fitted with a

door indicator switch. This switch

is rated 240V 0.5A AC Max. Power

load 50W Max. This switch is NOT

intended as a primary safety

device. Under normal operation the

pump door is kept closed and this

meets all statutory requirements

as a tool lockable fixed guard.
The switch may be used directly to

indicate that the door is open

during maintenance, or it may be

wired, following accepted fail safe

practices, into a customers start

up/shut down control system to

provide a back up to the Fixed Guard, whilst maintenance is being

carried out. However, all normal maintenance safety practices should

also be observed.
There are dangerous voltages (at mains potential) inside the motor. If

access is required, isolate the pump from the mains before removing the

cover.