Installation Guide

Surface Mount Raised Floor Grommets

General Information

SAFETY REQUIREMENTS

Installers must be familiar with standard safety and risk management practices when working in raised-floor environ-
ments and when modifying floor tiles.

Effective Installation of Cables

In order to minimize any air loss from the rack hole selection, make sure to allow for adequate slack in the cables. If
the cables are under too much tension, the grommet may be pulled apart, resulting in a gap that will cause an increase
in the flow of air escaping through the rack.

Maintaining Proper Cooling of Equipment

Failure to follow computer manufacturer’s guidelines for maintaining proper cooling may result in the overheating of
equipment. Before sealing cable cutouts, ensure that there is adequate airflow to the intake sides of computer equip-
ment or cabinets through devices such as perforated floor tiles or grates. Achieving proper airflow to the intake side of
the computer equipment and/or cabinets is the responsibility of the customer.

Dimensions and Tile Cutting Requirements

Inches (W x D x H)

Millimeters (W x D x H)

Part No. 2020 Original - Overall size

11” x 8

1/4

” x 1

1⁄8

279 x 210 x 29mm

Product height above the raised floor

1

1⁄4

” with mounting system installed

32mm

Maximum cutout size sealed

10” x 7

1/4

254 x 184mm

Usable cable area

33 sq in

21336 sq mm

Part No. 2030 Large - Overall size

12” x 11

3/4

” x 1

5⁄16

305 x 298 x 33mm

Product height above the raised floor

1

7⁄16

” with mounting system installed

37mm

Maximum cutout size sealed

10” x 9

3/4

254 x 248mm

Usable cable area

33 sq in

21336 sq mm

Part No. 2040 XLarge - Overall size

12” x 15” x 1

5⁄16

305 x 381 x 33mm

Product height above the raised floor

1

7⁄16

” with mounting system installed

37mm

Maximum cutout size sealed

10” x 13”

254 x 330mm

Usable cable area

33 sq in

21336 sq mm