Installation procedures – Thermon FAK-4L Kit User Manual
Page 3

The Terminator ZT / FAK-4L Thermostat In-Line Power
Kit is designed to provide accurate control with the ZT
thermostat and make a waterproof seal over the end of
TubeTrace and terminate Thermon electric heat trace in
an approved Terminator junction box. Review Instructions
prior to installation. Kit will make one connection.
2
Installation Precautions . . .
• Keep ends of bundles, heat tracing and kit components
dry before and during installation.
• To minimize the potential for arcing on electrical
heat tracing caused by product damage or improper
installation, use appropriate ground-fault circuit
protection.
• Installation must comply with Thermon requirements
and be installed in accordance with any applicable
national and local codes.
• Component approvals and performance ratings are
based on the use of Thermon specifi ed parts only. User
supplied power connection fi ttings must be listed or
certifi ed for intended use.
• De-energize all power sources before opening
enclosure.
• Individuals installing these products are responsible
for complying with all applicable safety and health
guidelines. Proper personal protective equipment, or
PPE, should be utilized during installation. Contact
Thermon if you have any additional questions.
Terminator ZT Certifi cations/Approvals . . .
INSTALLATION PROCEDURES
1725 II 2 GD Ex db eb IIC T5-T6, Ex tb IIIC T100°C-T85°C FM10ATEX0058X
IP66 -60°C Ta +50°C T5, 100°C; -60°C Ta +40°C T6, 85°C
Ordinary & Hazardous Locations
FMG 10.0022X Ex db eb IIC T5-T6, Ex tb IIIC T100°C-T85°C
2.
Trim tubing to within 85mm (3-1/4”) of the
end of the insulation. If self regulating heat
trace proceed to step 3. For Zone-type heat trace
continue with identifi cation of bus connection on
step 2a.
1.
Remove outer jacket and insulation from tubing
bundle approximately 508mm (20”) from end of
the tubing bundle.
508mm
(20”)
Tubing Bundle
85mm
(3-1/4”)
2a.
Strip back bundle insulation 85mm (3 1/4”)
beyond bus connection indentation of each heat
tracing. If bus connection indentation is less than
305mm (12”)-381mm (15”) from end of the heat
tracing, proceed stripping the bundle insulation
to the next indentation. Trim tubes so the bus
connection indentation on each meet.
Tubing
3.
Make tube fi tting connections with appropriate
fi tting (provided by others). Test fi tting for leaks
before proceeding. Mount tube fi tting shifted
from each other in case of multiple tubes.
508mm
(20”)
Tubing
Heat Tracing
Self-Regulating Heat Tracing
Zone Type Heat Tracing
85mm
(3-1/4”)
Tubing
Heat Tracing
305mm -381mm
(12” - 15”)
Bus Connection
Indentations
(Zone Heater Only)
Tube Fitting
(Provided by Others)
Heat Tracing
Heat Tracing
CAUTION
(Found on TubeTrace SE/ME bundles)
Do not cut or damage the heat
trace or sampling tube.
5.
Cut splice cover ends to match outside diameter
of tubing bundle. For bundle diameter less than
48mm remove only the closed in part.
Splice Cover
Top
Tubing
Bundle
Cut and Remove
End Pieces to fi t
Heat Tracing
Splice Cover
Base
4.
Cut the ends of the cable at an angle to aid in
piercing grommet.
45°
Heat Tracing